Skip to main content

Table 1 Insulation aging acceleration factor for continuous operation at the hottest spot temperature during one load cycle [33]

From: Fuzzy logic applied to the diagnosis of technical conditions of distribution transformers

Hottest spot temperature °C (HST)

Insulation aging acceleration factor (IAAF)

110

1.00

120

2.71

130

6.98

140

17.2

150

40.6

160

92.1

170

201.2

180

424.9

190

868.8

200

1723