Item | Value | Unit |
---|---|---|
AHU #1 to cool the air intake to GT | 69,473 | MMBtu/year |
AHU #2 to serve cooling load of the switchgear building | 4883 | MMBtu/year |
AHU #3 to serve cooling load of the DCS building | 2930 | MMBtu/year |
Total avoided energy | 77,286 | MMBtu/year |
Fuel gas cost | 4.75 | US$/MMBtu |
Total avoided energy costs | 367,000 | US$/year |
GHG emission reduction | 4100 | Ton CO2-eq/year |
Energy reduction to total energy input | 15.3 | % |