Skip to main content

Table 10 Estimated investment cost—WHR system

From: Energy efficiency and greenhouse gas emission abatement opportunities for an existing gas treatment plant: a comprehensive technical and economic analysis

Description

USD

Exhaust gases main manifold for 2 GTs furnished by 5 modulated exhaust dampers—the manifold is sized for 33.8 kg/s flue gases

313,000

Waste heat recovery hot water generator—capacity of 1 MWthermal

95,000

Waste heat recovery hot oil generator—capacity of 3.25 MWthermal

277,000

Re-boiler of hot oil driven type—capacity 2.8 MWthermal

357,000

Absorption chiller of 220 TOR capacity

138,000

Cooling tower of 410 tor capacity

68,000

Chilled water pumps at 110 m3/h, 40 m head

30,000

Condenser water pump at 125 m3/h, 40 m head

33,000

AHU#1 for cooling air intake to gas turbine (150 TOR)

42,000

AHU#2 for cooling switchgear building (40 TOR)

21,000

AHU#3 for cooling DCS building (24 TOR)

15,000

Sub-total investment cost

1,389,000

Balance of the system

97,000

Engineering and overhead costs

67,000

Extra installation work cost

208,000

Total investment cost

1,761,000